ioLogik R2140 User’s Manual Modbus/TCP Address Mappings
Address Data Type Description
0x0019 1 word CH5 AI PowerOn Range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Others: return Illegal Data Value
0x001A 1 word CH6 AI PowerOn Range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Others: return Illegal Data Value
0x001B 1 word CH7 AI PowerOn Range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Others: return Illegal Data Value
0x001C 1 word CH0 AI Safe Range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Others: return Illegal Data Value
0x001D 1 word CH1 AI Safe Range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Others: return Illegal Data Value
0x001E 1 word CH2 AI Safe Range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Others: return Illegal Data Value
B-6