4-17
MGate™ 4101-MB-PBS Series
Industrial Ethernet
Industrial Ethernet Gateways >
Ordering Information
Dimensions
Unit: mm (inch)
Available Models
MGate 4101-MB-PBS: 1-port Modbus-to-PROFIBUS slave gateway, 12-48 VDC, 0 to 60°C operating
temperature
MGate 4101I-MB-PBS: 1-port Modbus-to-PROFIBUS slave gateway with 2 kV isolation, 12-48 VDC,
0 to 60°C operating temperature
MGate 4101-MB-PBS-T: 1-port Modbus-to-PROFIBUS slave gateway, 12-48 VDC, -40 to 75°C
operating temperature
MGate 4101I-MB-PBS-T: 1-port Modbus-to-PROFIBUS slave gateway with 2 kV isolation, 12-48 VDC,
-40 to 75°C operating temperature
Optional Accessories (can be purchased separately)
DR-4524: 45W/2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
DR-75-24: 75W/3.2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
DR-120-24: 120W/5A DIN-rail 24 VDC power supply with 88 to 132 VAC/176 to 264 VAC input by switch
WK-36-02: Wall mounting kit
Package Checklist
• 1 MGate 4101-MB-PBS or 4101I-MB-PBS
Modbus-to-PROFIBUS slave gateway
• Documentation and software CD
• Quick installation guide (printed)
• Warranty card
• RJ45 to DB9 cable (for console use)
Serial Signals
RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422: Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w: Data+, Data-, GND
Software
Conguration Options: Serial Console, Windows Utility
Utilities: MGate Manager for Windows 2000/XP/2003/Vista/Server
2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Support: QuickLink, Paging
Physical Characteristics
Housing: Metal, IP30 protection
Weight: 500 g
Dimensions: 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)
Environmental Limits
Operating Temperature:
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Altitude: Up to 2000 m (795 hPa), higher altitudes on demand
Note: Please contact Moxa if you require products guaranteed to function
properly at higher altitudes.
Power Requirements
Input Voltage: 12 to 48 VDC
Power Connector: Terminal block
Power Consumption:
MGate 4101-MB-PBS: 340 mA @ 12 VDC, 130 mA @ 48 VDC
MGate 4101I-MB-PBS: 375 mA @ 12 VDC, 140 mA @ 48 VDC
Standards and Certifications
Safety: UL 60950-1, EN 60950-1
Hazardous Location:
UL/cUL Class 1 Division 2 Groups A/B/C/D (Pending),
ATEX Zone 2 Ex nA nC IIC T3 Gc (Pending),
IECEx (Pending)
EMC: CE, FCC
EMI: EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS:
EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 3,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 1
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Reliability
MTBF (mean time between failures): 513,139 hrs
Warranty
Warranty Period: 5 years
Details: See www.moxa.com/warranty
Rear ViewTop View Front View Side View
Dual power inputs and relay output
DIN-rail
105.04 (4.14)
36 (1.42)
4.3 (0.17)
149.25 (5.88)
140 (5.51)
113.84 (4.48)
Reset to default button
Rotary switches
LED indicators
Serial console
Modbus serial port
PROFIBUS port